| Degree of protection (IP) | IP20 |
|---|---|
| Shock | 10 G peak for 11 ms duration (??1.0 ms) |
| PWM frequency | 4 kHz @ 650V DC |
| Vibration | 0.152 mm (0.006 in.) displacement, 1 G peak, 5.5 Hz |
Electrical
| Number of analogue outputs | 2 |
|---|---|
| Mains voltage | 480 V |
| Integrated breaking resistance | No |
| Max. output voltage | 932 V |
| Internal dynamic brake resistors | 115 Ohm |
| DC bus overvoltage trip | 810V DC @ 480V |
| DC nominal bus voltage | 648V DC @ 480V |
| Brake IGBT | Brake IGBT installed |
| Internal communication module | No communication module |
| Fuse current rating | 40 A @ 650V DC |
| Input voltage rating | 480V AC, 3-phase, 60 Hz |
| Displacement power factor | 0.98 across speed range |
| Output current, continuous | 22 A @ 650V DC |
| Output current, 1 min | 24.2 A @ 650V DC |
| Output current, 3 sec | 33 A @ 650V DC |
| Circuit breaker current rating, max | 80 A @ 480V AC, 3-phase |
| Motor circuit protector current rating, max | 30 A @ 480V AC, 3-phase |
| Logic control ride-thru | 0.25 seconds, drive not running |
| Brake resistor | No internal brake resistor |
| Input current rating | 23.3 A @ 650V DC |
| Rated power rating | 15 Hp @ 650V DC, normal duty |
| Documentation | English documentation |
| Carrier frequency | Drive rating: 4 kHz, settings: 2, 4, 6, 8, 10 kHz (6 kHz is for V/Hz operation only) |
| AC input overvoltage trip | 600V AC @ 480V (six pulse, 3-phase) |
| Input power rating | 16.6 kVA @ 480V AC, 3-phase |
| Electronic motor overload protection | Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C file E59272 |
| Dual element time delay fuse current rating | 25…50 A @ 480V AC, 3-phase |
| Non-time delay fuse current rating | 25…80 A @ 480V AC, 3-phase |
| Heat sink thermistor | Monitored by microprocessor overtemperature trip |
| Drive to motor power ratio, max | The drive to motor rating cannot exceed a 2:1 ratio |
| Stop modes | Multiple programmable stop modes including ?C Ramp, Coast, and Current Limit |
| Acceleration/deceleration | Independently programmable accel and decel times adjustable from 0 to 6553.5 in 0.1 second increments |
| Number of digital inputs | 6 |
| Number of digital outputs | 2 |
| Number of analogue inputs | 3 |
| Motor voltage, nom | 460V @ 380…400V drive rating, 480V nominal line voltage |
| Human interface model | No HIM (no blank plastic inserted) |
| Additional configuration | Phase II control |
| Max. output frequency | 400 Hz |
| Line voltage, nom | 480V @ 380…400V drive rating, 460V nominal motor voltage |
| Mains frequency | 60 Hz |
| Internal EMC filtering | With EMC filter & common mode choke |
| Watt loss | 389 W @ 480V AC, 15 Hp normal duty, 10 Hp heavy duty |
| Feedback option | Future use |
| Drive full power range | 460…528V @ 380…400V drive rating, 460V nominal motor voltage |
| Drive operating range | 325…528V @ 380…400V drive rating, 460V nominal motor voltage |
| Torque regulation | Torque regulation – without feedback: ??5%, 600 rad/sec bandwidth |
| Enclosure type | IP20/NEMA/UL Type 1 |
| Output current rating | 22 amps, 15 Hp normal duty, 10 Hp heavy duty, frame 1 |
| Control options | Phase II control, expanded cassette |
| Drive overcurrent trip | Software current limit: 105% of motor rated to 200% of drive rated current |
| Efficiency | 97.5% at rated amps, nominal line volts |
| Speed control | Speed regulation – without feedback: 0.1% of base speed across 120:1 speed range, 120:1 operating range, 50 rad/sec bandwidth |
| Current limit capability | Independent motoring and regenerative power limits programmable to 800% of rated output current |
| Selectable motor control | Field oriented control with and without a feedback device and permanent magnet motor control |
| Input phases | Six-pulse, 3-phase input provides full rating for all drives, single-phase operation provides 50% of rated current |
| Control method | Induction motor and brushless motor: sine coded PWM with programmable carrier frequency, indirect self organized, field-oriented control, current-regulated, ratings apply to all drives, refer to the PowerFlex 700S Phase ll control reference manual, public |
| Number of phases output | 3 |
| Number of phases input | 3 |
| Relative symmetric net voltage tolerance | 10 % |
| Input frequency, max | 400 Hz |
| Output frequency range | 0 Hz |
| DC bus undervoltage trip | Adjustable |
| Output voltage range | 0 to rated motor voltage |
| Power ride-thru | 15 milliseconds at full load |
| S-curve time | Adjustable 0.5…4.0 seconds |
| Short circuit trip | Phase-to-phase on drive output |
| Ground fault trip | Phase-to-ground on drive output |
| Control logic noise immunity | Showering arc transients upto 1500V peak |
| Line transients | Up to 6000 volts peak per IEEE C62.41-1991 |
| Intermittent overload | 110% overload capability for up to 1 minute, 150% overload capability for up to 3 seconds |
| Short circuit current, max | Using recommended fuse or circuit breaker type: maximum short circuit current rating to match specified fuse/circuit breaker capability ??200000 Amps |
| Encoder voltage supply | 5V DC or 12V DC 320 mA/channel, 5V DC minimum high state voltage state of 0.4V DC, 12V DC minimum high state voltage of 7.0V DC, maximum low state voltage of 0.4V DC |
Construction
| Height, approx | 336 mm |
|---|---|
| Depth, approx | 200 mm |
| Width, approx | 166.9 mm |
| Weight, approx | Drive: 7.03 kg |


Đánh giá
Chưa có đánh giá nào.