Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40 ??C ?? Ta ?? +70 ??C (-40 ??F ?? Ta ?? +158 ??F)
Temperature, surrounding air, max 70 ??C (158 ??F)
Enclosure type rating None (open-style)
Input range, voltage
??10V DC
0…10V DC
0…5V DC
Input range, current 0…20 mA
4…20 mA HART
Backplane power (BP) voltage 15V DC
Backplane power (BP) current, max 35 mA
Sensor actuator power (SA) voltage range 18??32V DC
Sensor actuator power (SA) current, max 350 mA (Includes per channel SSV output 21 mA @25V for 2-wire HART device loop power)
Isolation voltage
250V (continuous), Basic Insulation Type, System to Field
SA to channel/SSV, SA to FE
Channel to channel, Channel to FE
Wire category(1)
(1) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Group D industrial use
Limited to 10 A
300V/10A
UL94V-0
Wire size 0.34??2.5 mm2
(22??14 AWG) solid or stranded copper wire rated at 105 ??C (221 ??F), or greater, 1.2 mm (3/64 in.) insulation max
Insulation stripping length
Screw-type TB:
? 0.34…2.5 mm2
(22??14 AWG) = 12 mm ?? 1 mm (0.47 ?? 0.04 in.)
Spring-type TB:
? 0.34…1.5 mm2
(22…16 AWG) = 10 mm ?? 1 mm (0.39 ?? 0.04 in.)
? 2.5 mm2
(14 AWG) = 15 mm ?? 1 mm (0.59 ?? 0.04 in.)
Terminal base
5094-MB plus 5094-RTB3I (referred to in documentation as a non-orderable 5094-TB3I)
5094-MB plus 5094-RTB3IS (referred to in documentation as a non-orderable 5094-TB3IS)
5094-MBXT plus 5094-RTB3IXT (referred to in documentation as a non-orderable 5094-TB3IXT)
5094-MBXT plus 5094-RTB3ISXT (referred to in documentation as a non-orderable 5094-TB3ISXT)
TB keying
TB torque Screw-type TB: 0.4 N?m (3.5 lb?in)
Spring-type TB: Not applicable
North American temp code T4
UKEX/ATEX temp code T4
IECEx temp code T4
Corrosion resistance classification 5094-IF8IH ?C ISA S71.04 G2
THƯ VIỆN ẢNH